Details: earthing set suitable for lt line made of gi pipe 25 mm dia (internal dia) wall thickness 3.25mm medium quality pipe of standard make confirming to is: specifications 2000mm long with gi socket closed at top pipe shall have holes of 12 mm dia every 150 mm apart throughout the length and staggered diametrically . full clamps of ms flat 40x3mm fitted at top end of the pipe along with bolts and nuts size 50x12mm and washers for fixing the clamp on the pipe. the bottom end of the pipe shall be tapered cut at 45 degree earthing set suitable for ht line made of gi pipe 40mm dia (internal dia) wall thickness 3.25mm medium quality pipe of standard make confirming to is: specifications 2500mm long with gi socket closed at top pipe shall have holes of 12 mm dia every 150 mm apart throughout the length and staggered diametrically. full clamps of ms flat 40x3mm fitted at top end of the pipe along with bolts and nuts size 50x12mm and washers for fixing the clamp on the pipe. the bottom end of the p