Details: internal wiring"supply, installation, testing and commissioning of lt cubicle type totally enclosed free standing type, dust, damp and vermin proof main distribution board complete with busbars, m.v. danger notice plate,space heater, power outlet, illumination lamp, multifunction meter indicating lamps, ct's, interconnections, with suitable capacity aluminium leads / solid aluminium strips / rods, connection of incoming and outgoing cables with thimbles, stove enameled painted and having following incoming and outgoing mccbcomplete as required. mltp panelincomer:1nos. 400 a 4p microprocessor based mccb of 36ka with rotary handle, shunt trip coil, adjustable o/l, s/c, e/f release.1 nos. digital type multifunction meter and indicators 2 set of r,y,b led phase indicating lamp with mcb protection.1 set of on,off & trip led indicating lamp with mcb protection.busbars:630 amp tpn (25ka for 1sec) aluminium busbar chamber of suitable length with aluminium busbars. all busbars and interconn
Sector: University