Details: point wiring using copper wire without switch. supplying and wiring adopting loop system in existing pvc conduit /casing capping casing capping using 2x1.5sqmm (phase & neutral) & 1x1.0 sqmm (earth wire) frls multi strand pvc insulated copper wire (confirming to is-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/pvc round block. complete for each outlet. short point up to 3mtr from tapping point to out let via switch;point wiring using copper wire without switch. supplying and wiring adopting loop system in existing pvc conduit /casing capping casing capping using 2x1.5sqmm (phase & neutral) & 1x1.0 sqmm (earth wire) frls multi strand pvc insulated copper wire (confirming to is-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficien